Viessmann · Boiler troubleshooting
Heating circuit supply control and DHW priority
What is going on
Heating circuit supply is set from the outdoor temperature, set room temperature, operating mode and heating curve. The DHW priority setting decides what happens to the heating circuit while the tank heats.
Check in this order
- Set coding a2 in the Heating circuit group to choose priority mode.
- With priority control (a2:2), the heating circuit set supply drops to 32°F (0°C) during tank heating, the mixing valve closes and the heating pump switches off.
- Without priority control, the heating circuit keeps the same set value.
- With modulating priority and a mixing valve, the heating pump stays on and the supply is lowered until the boiler water set point is reached.
Applies to: Heating circuits with and without mixing valves on CA3B Dual Fuel
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 39-40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.