Coco OT single boiler DIP setting and connection

Versatronik 200

What is going on

Single boiler installations use one Coco OT with DIP switch setting for a single boiler. The Coco OT is wired to the CAN connections, and DHW can be handled on the CAN side.

Check in this order

  1. Wire H and L to the CAN BUS terminals, observing polarity.
  2. Wire + and - to the CAN power supply terminals.
  3. Set the DIP switches to the single boiler setting (see the DIP switch setting table).
  4. Plug in the 4-pole connector after the interconnections are done.

Applies to: Single modulating boiler with Coco OT

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation and operating manual, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.