Viessmann · Boiler troubleshooting
Burner does not switch on
What is going on
Burner does not light even though the boiler is requested.
Likely causes
- Heating program 9 is set (its button is lit)
- Vitoair draught stabilizer defective (pressure jet burner only)
- Motor-controlled flue gas damper failure (gas boiler with atmospheric burner)
- Fault on the control unit
Check in this order
- Set the rw heating program (see page 10 of the manual).
- Inform the heating contractor if the Vitoair or flue gas damper has failed.
- Only if the heating contractor instructs it: put the Vitoair or flue gas damper in manual operation by pressing in rotary knob A and turning it fully beyond setting 4.
- For a control unit fault, see the fault on control unit guide.
Applies to: Vitotronic 100, GC1 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.