Set expansion tank and system pressures

Vitorond 200 VD2

What is going on

Follow the expansion tank maker's instructions. Max operating pressure is 75 psig (5 bar), or 58 psig (3.9 bar) in some Canadian provinces.

Likely causes

  • Low inlet pressure in the expansion tank

Check in this order

  1. Drain the system or close the cap valve on the expansion tank and bleed the tank pressure to 0 psig.
  2. If the tank inlet pressure is below the static system pressure, add nitrogen until the inlet is 1.5 to 3 psig (0.1 to 0.2 bar) above static.
  3. Fill with water until the cold fill pressure is 1.5 to 3 psig (0.1 to 0.2 bar) above the tank inlet pressure.
  4. Do not exceed 75 psig (5 bar), or 58 psig (3.9 bar) where required.
  5. Check that the sight glass gasket and hose are airtight.
  6. Test water hardness and treat the water if the mineral content is high.

Applies to: All VD2 sizes 320 to 1080

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.