Rinnai · Boiler troubleshooting

Enable simultaneous central heating and domestic hot water

I-Series Plus

What is going on

By default the boiler gives domestic hot water priority. Simultaneous operation divides flow between the DHW plate heat exchanger and the central heating circuit.

Check in this order

  1. Remove the front panel by removing the two screws.
  2. Locate the PC board and the left PC board button.
  3. Press and hold the button for five seconds.
  4. Set parameter 08 to b to enable simultaneous central heating and DHW.
  5. Set parameter 14 and 15 as required (see the simultaneous operation setting).
  6. Confirm the central heating system is designed for the higher supply temperature if parameter 14 is set to b.

Applies to: I-Series Plus Condensing Combi Boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 103. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.