Viessmann · Boiler troubleshooting
Cleaning the brazed plate heat exchanger (B1KE)
What is going on
Chemical cleaning of the DHW side of the plate heat exchanger using a circulating pump and cleaning solution.
Likely causes
- Fouling or scaling from hard water at high temperatures
Check in this order
- Disconnect electrical power to the boiler.
- Close the shutoff valves and isolate the boiler water from the heating system and the cold water inlet.
- Fill a pail with about 5 gallons of new food grade white vinegar or citric acid.
- Place the discharge hose and the inlet hose into the pail.
- Connect the other ends of the hoses to the heat exchanger.
- Open both drain valves.
- Run the pump for at least 60 minutes to circulate the solution through the DHW side, then turn it off.
- Empty the pail and fill it with clean potable water.
- Rinse the DHW side by circulating clean water for at least 7 minutes. Repeat if necessary.
- Close the drain valve, disconnect the hoses and return the system to service.
Applies to: B1KE plate heat exchanger, DHW side
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 84. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.