Cleaning the brazed plate heat exchanger (B1KE)

Vitodens 100-W B1HE/B1KE

What is going on

Chemical cleaning of the DHW side of the plate heat exchanger using a circulating pump and cleaning solution.

Likely causes

  • Fouling or scaling from hard water at high temperatures

Check in this order

  1. Disconnect electrical power to the boiler.
  2. Close the shutoff valves and isolate the boiler water from the heating system and the cold water inlet.
  3. Fill a pail with about 5 gallons of new food grade white vinegar or citric acid.
  4. Place the discharge hose and the inlet hose into the pail.
  5. Connect the other ends of the hoses to the heat exchanger.
  6. Open both drain valves.
  7. Run the pump for at least 60 minutes to circulate the solution through the DHW side, then turn it off.
  8. Empty the pail and fill it with clean potable water.
  9. Rinse the DHW side by circulating clean water for at least 7 minutes. Repeat if necessary.
  10. Close the drain valve, disconnect the hoses and return the system to service.

Applies to: B1KE plate heat exchanger, DHW side

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 84. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.