Preventing oxygen corrosion in the heating water
What is going on
Oxygen in the heating water causes corrosion. Keep the system sealed and at positive pressure, and avoid gas-permeable components.
Likely causes
- Open vented expansion vessels with flow through them
- Negative pressure in the system
- Gas-permeable components such as some plastic pipes in underfloor heating
Check in this order
- Keep the system pressure above atmospheric pressure at all points, including the pump suction side.
- Check the expansion vessel precharge at least during the annual service.
- Separate permeable plastic pipe circuits from the boiler with a corrosion-resistant heat exchanger.
- Where oxygen ingress is a risk, use an oxygen binder such as sodium sulphite at 5 to 10 ppm (5 to 10 mg/L).
- Keep the heating water pH between 8.2 and 9.5.
- Refer chemical treatment questions to a qualified water treatment contractor.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.