Application 3: single-temperature zoning with zone pumps and indirect DHW
What is going on
Four-zone single-temperature system with an indirect water heater. A thermostat call energizes that zone's pump through the multi-zone control. The heat demand output feeds the DE1 input of the EA1 module, which creates a ZC1 set point demand. Intended as a simple control solution for single-temperature applications.
Check in this order
- Select 1 Zone Circuit in the menu because this is a single-temperature circuit.
- Press OK to confirm. No pump is assigned in this application, so no pump output is selected.
- Confirm the zone circuit summary shows no pumps selected.
- Enter the target water temperature the boiler uses on a zone call for heat, then press OK.
- Set the DHW timer as needed. If DHW can be produced at any time, set the timer to 0:00 to 24:00.
Applies to: Application code VD2T 2ZC2T2ZP.01 (Application 3, pages 40-41)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 222-F B2TB application guide, p. 40-41. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.