Application 3: single-temperature zoning with zone pumps and indirect DHW

Vitodens 222-F

What is going on

Four-zone single-temperature system with an indirect water heater. A thermostat call energizes that zone's pump through the multi-zone control. The heat demand output feeds the DE1 input of the EA1 module, which creates a ZC1 set point demand. Intended as a simple control solution for single-temperature applications.

Check in this order

  1. Select 1 Zone Circuit in the menu because this is a single-temperature circuit.
  2. Press OK to confirm. No pump is assigned in this application, so no pump output is selected.
  3. Confirm the zone circuit summary shows no pumps selected.
  4. Enter the target water temperature the boiler uses on a zone call for heat, then press OK.
  5. Set the DHW timer as needed. If DHW can be produced at any time, set the timer to 0:00 to 24:00.

Applies to: Application code VD2T 2ZC2T2ZP.01 (Application 3, pages 40-41)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 222-F B2TB application guide, p. 40-41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.