Relief valve installation and discharge piping

CGi Series 5

What is going on

Install the relief valve upright in the ¾-inch tapping on the side of the boiler. Discharge piping must be short, full size, pitched down, and end in a visible, safe location. Failure to follow these rules can stop the valve from working.

Likely causes

  • Shutoff valve installed between relief valve and boiler
  • Discharge line blocked, plugged or threaded at the end
  • Discharge line freezing or ending in an unsafe place

Check in this order

  1. Mount the relief valve vertically in the ¾-inch side tapping (see Figure 15 or 16 and the valve tag).
  2. Run the discharge line from the valve outlet to a safe disposal point.
  3. Keep the discharge line as short as possible and the same size as the valve outlet along its full length.
  4. Pitch the discharge line down from the valve and end it at least 6 inches above a floor drain where discharge will be visible.
  5. End the discharge line plain (not threaded) with material rated for 375°F or higher.
  6. Do not pipe the discharge where freezing can occur.
  7. Do not install any shutoff valve between the relief valve and boiler or in the discharge line.
  8. Do not plug or block the discharge line.
  9. After filling and pressurizing, lift the lever to test the valve. Confirm it discharges freely. Replace the valve if it does not operate correctly.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.