Rinnai · Boiler troubleshooting
Heating system warms without a call
What is going on
The radiators or baseboard feel warm or even hot while the thermostats aren't calling. Two things cause it most of the time: the pump is set to run continuously, or the three-way valve isn't shutting off the heating side properly.
Likely causes
- Pump program key on (continuous circulation)
- Dirt or binding in the three-way valve or cartridge
Check in this order
- Switch the pump program off.
- After changing it, give the system 15 to 20 minutes with no call and see whether the radiators cool down.
- If they stay hot, clean or replace the three-way valve.
- Let the system cool down and isolate it before pulling the cartridge so you don't get scalded.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.77 (15.4). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.