Viessmann · Boiler troubleshooting
Boiler and DHW tank sensor connection
What is going on
The boiler sensor is installed with the boiler insulation. The DHW tank sensor is used only on systems with domestic hot water heating and must not be connected otherwise.
Check in this order
- Connect the boiler temperature sensor plug to socket 3 and fit the molded strain relief clamp.
- On systems without DHW heating, do not connect the DHW tank sensor to the control.
- On systems with DHW heating, install the DHW tank sensor in the tank, pressing it firmly against the sensor well wall.
- Connect the DHW tank sensor plug to socket 5 and fit the molded strain relief clamp.
- Check that the maximum DHW temperature cannot be exceeded. Add an extra safety high limit or an approved tempering valve if needed.
Applies to: Boiler temperature sensor and DHW tank temperature sensor, Vitotronic 300
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 installation instructions, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.