Viessmann · Boiler troubleshooting

Access the burner and disconnect the burner control

Vitocrossal 200 CM2

What is going on

Preparation steps before working on the burner.

Check in this order

  1. Close the main gas supply valve.
  2. Switch off the main power switch and confirm power is off.
  3. Remove the front panel and side panels per the boiler installation instructions.
  4. Remove plugs 41 and 90 from the burner control and plugs 40/156, 40 and 53 from the burner bracket.
  5. Remove plugs from the electrodes.
  6. Remove the air intake adaptor and air flex hose.
  7. Open the gas connection to the burner.
  8. Loosen the four M12 bolts and open the burner door.
  9. Loosen the two programming unit screws, lift the unit off and disconnect its cable.
  10. Disconnect all cables from the burner control sub-base.

Applies to: Burner control and burner door

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.