Viessmann · Boiler troubleshooting

Service interval message on the display

Vitodens 200-W B2HA

What is going on

After the service limits in coding addresses 21 and 23 are reached, the red fault indicator flashes and the display shows Service with the service symbol.

Likely causes

  • Hours run or time interval limit set in coding 21 or 23 has been reached.

Check in this order

  1. Press OK to acknowledge the service message.
  2. Note an acknowledged message that was not reset comes back on the following Monday.
  3. After the service is done, press OK and the second key together for about 4 seconds.
  4. Select Service functions, then Service reset.
  5. The hours run and time interval counters restart at 0.

Applies to: Vitodens 200-W B2HA 45, 60

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 37. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.