Display normal but DHW not hot enough
What is going on
Display normal, hot water runs, but it comes out lukewarm at the tap. Usually a setting, sometimes the mixing valve.
Likely causes
- DHW setpoint set too low for the DHW mode
- Faulty or misadjusted thermostatic mixing valve
- Mixing valve set to blend in too much cold water
Check in this order
- Raise the DHW setpoint to the recommended value for the DHW mode (see the DHW setpoint table in this section).
- Check the thermostatic mixing valve for proper operation.
- Measure tap temperature with a thermometer after a minute of flow.
- Any DHW setting above 120°F requires a thermostatic mixing valve, so do not raise it without one because of scald risk.
Applies to: C95 & C140 Glow Combi boilers
More boiler guides
Related
Glow Brand error codes · Glow Brand parts · Glow Brand tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: C-300 C95-C140 Installation & Operation Manual, p. 74. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.