Viessmann · Boiler troubleshooting
Check the supply temperature sensor (strap-on or immersion)
What is going on
The supply sensor plugs into socket ? on the control unit. Check it by resistance against the current supply temperature.
Likely causes
- Sensor reading differs significantly from actual temperature
Check in this order
- Disconnect plug ? in the terminal compartment.
- Measure the sensor resistance at terminal 2 of the plug.
- Compare the reading with the current temperature using the resistance table.
- If the value differs significantly, check the installation and replace the sensor if needed.
Applies to: Common supply temperature sensor
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 79. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.