Viessmann · Boiler troubleshooting

Check the supply temperature sensor (strap-on or immersion)

Vitocontrol-S VD2/CT3/CM2

What is going on

The supply sensor plugs into socket ? on the control unit. Check it by resistance against the current supply temperature.

Likely causes

  • Sensor reading differs significantly from actual temperature

Check in this order

  1. Disconnect plug ? in the terminal compartment.
  2. Measure the sensor resistance at terminal 2 of the plug.
  3. Compare the reading with the current temperature using the resistance table.
  4. If the value differs significantly, check the installation and replace the sensor if needed.

Applies to: Common supply temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 79. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.