Viessmann · Boiler troubleshooting

Update participant list (Vitocontrol-S cascade)

Versatronik 505 NR2/BACIPVersatronik 505D NR2/BACIP

What is going on

Run this after all communication connections are made, with the Vitocontrol-S coded as error manager (default). Each gateway needs a unique LON participant number set on its rotary dial.

Check in this order

  1. Confirm the Vitocontrol-S is coded as error manager (see Vitocontrol-S manual, address 79:01).
  2. Check that no two gateways share a rotary dial LON participant number.
  3. Press OK and Menu together to open the Service screen, then press OK.
  4. Arrow down to Service Functions and press OK.
  5. Make sure Subscriber Check is highlighted, then press OK.
  6. Arrow down to Delete List? and press OK.
  7. Wait for devices to report back, then run the subscriber check again.

Applies to: Vitocontrol-S cascade control with Versatronik 505 gateways

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 505 and 505D BACnet IP manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.