Update participant list (Vitocontrol-S cascade)
What is going on
Run this after all communication connections are made, with the Vitocontrol-S coded as error manager (default). Each gateway needs a unique LON participant number set on its rotary dial.
Check in this order
- Confirm the Vitocontrol-S is coded as error manager (see Vitocontrol-S manual, address 79:01).
- Check that no two gateways share a rotary dial LON participant number.
- Press OK and Menu together to open the Service screen, then press OK.
- Arrow down to Service Functions and press OK.
- Make sure Subscriber Check is highlighted, then press OK.
- Arrow down to Delete List? and press OK.
- Wait for devices to report back, then run the subscriber check again.
Applies to: Vitocontrol-S cascade control with Versatronik 505 gateways
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 505 and 505D BACnet IP manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.