Viessmann · Boiler troubleshooting
Convert fuel type from natural gas to liquid propane
What is going on
Field conversion of both gas valves and coding for LPG operation.
Check in this order
- Set adjusting screw A at the gas valve to 2 with a 2.5 mm hex key.
- Switch ON/OFF switch 8 to ON by sliding the black control cover outward.
- Enter coding level 2 and select 'General'.
- Set coding address 11 to 9.
- Set coding address 82 to 1 for liquid propane.
- Return to coding address 11 and set any value except 9.
- Exit coding level 2 and open the gas shut-off valve.
- Apply the supplied fuel conversion labels.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.