Viessmann · Boiler troubleshooting
Clean the heat exchanger and refit the burner
What is going on
Clean the stainless steel heat exchanger without metal brushes. Discolouration is normal and does not affect function.
Check in this order
- Remove the burner assembly (see burner removal guide).
- Vacuum loose debris from combustion chamber A.
- Rinse sediment from stainless steel heat exchanger surface B with water or an approved cleaner. Keep the refractory dry.
- If coil gaps are blocked, remove debris with the Viessmann tool, without scratching the surface.
- Flush combustion chamber A with water until it runs clear through the condensate trap.
- Remove and clean debris from the condensate trap, then refit it (see page 25).
- Refit the burner (see burner reinstall guide).
Applies to: Vitodens 222-F B2TB 19, 35, 68, 125
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB service instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.