Weil-McLain · Boiler troubleshooting
Gas supply piping connection and sizing
What is going on
Install a union for servicing when required and a manual shutoff within 6 ft of the boiler, identified by the installer in Canada. Support gas piping with hangers, not the boiler. Size the supply from the meter outlet using the total connected input in Btuh divided by 1,000 for approximate cubic feet per hour, plus fitting equivalent lengths. Manifolded multiple boiler supplies need a manual shutoff, union and sediment trap at each boiler.
Check in this order
- Install a union for servicing if required.
- Install a manual shutoff valve within 6 ft of the boiler.
- Support the gas piping independently of the boiler and its accessories.
- Divide total connected input in Btuh by 1,000 to get approximate cubic feet per hour.
- Size the supply pipe using the gas capacity table and equivalent fitting lengths.
- On manifolded supplies, add a manual shutoff, union and sediment trap at each boiler, with the trap at least 3 in below the tee.
Applies to: SlimFit SF1000, SF1500, SF2000
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 45, p. 46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.