Low water cut-off (LWCO) wiring

Vitotronic 300

What is going on

A low water cut-off device is wired to the Power Pump Module. Its jumper must be removed first, and the function must be tested after installation.

Check in this order

  1. Run a 3-conductor cable from the low water cut-off device to the Power Pump Module.
  2. Remove the jumper between terminals L/P1 and P2 on the Power Pump Module board.
  3. Wire the device as shown in the manual. The contact closes on water.
  4. After installation, check that the LWCO function works.

Applies to: Low water cut-off device on Vitotronic 300 / Power Pump Module

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 installation instructions, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.