Viessmann · Boiler troubleshooting
Low water cut-off (LWCO) wiring
What is going on
A low water cut-off device is wired to the Power Pump Module. Its jumper must be removed first, and the function must be tested after installation.
Check in this order
- Run a 3-conductor cable from the low water cut-off device to the Power Pump Module.
- Remove the jumper between terminals L/P1 and P2 on the Power Pump Module board.
- Wire the device as shown in the manual. The contact closes on water.
- After installation, check that the LWCO function works.
Applies to: Low water cut-off device on Vitotronic 300 / Power Pump Module
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 installation instructions, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.