Weil-McLain · Boiler troubleshooting

Display blank but boiler operates (display communication lost)

ECO Tec Series 3

What is going on

Communication from the control to the display is lost.

Likely causes

  • Loose connection or poor pin engagement at plug J14.
  • Broken wire harness between display, communications board and control.
  • Failed display module.

Check in this order

  1. Check plug J14 and the back of the display board for loose connections and proper pin alignment.
  2. Check continuity on the wire harness from the display to the communications board to the control board.
  3. Cycle power off and on and check operation.
  4. Replace the display module with the correct part from the Parts section.

Applies to: ECO Tec Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 163. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.