Viessmann · Boiler troubleshooting

Checking the fixed high limit

Vitodens 222-F

What is going on

Check this if the burner control cannot be reset after a fault shutdown while the boiler water temperature is below about 167°F (75°C).

Check in this order

  1. Remove the cables from fixed high limit A.
  2. Check the continuity of the fixed high limit with a multimeter.
  3. Replace the fixed high limit if it is defective.
  4. After starting the boiler, press reset button R on the boiler control.

Applies to: Vitodens 222-F B2TB

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F B2TB service instructions, p. 86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.