Viessmann · Boiler troubleshooting
Checking the fixed high limit
What is going on
Check this if the burner control cannot be reset after a fault shutdown while the boiler water temperature is below about 167°F (75°C).
Check in this order
- Remove the cables from fixed high limit A.
- Check the continuity of the fixed high limit with a multimeter.
- Replace the fixed high limit if it is defective.
- After starting the boiler, press reset button R on the boiler control.
Applies to: Vitodens 222-F B2TB
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB service instructions, p. 86. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.