Hydrostatic leak test of the boiler

Vitorond 100VR1

What is going on

Test before the boiler is connected to piping or power. Do not exceed 1-1/2 times the maximum operating pressure.

Check in this order

  1. After installing the safety devices, fit a temporary cap on the 3/4 in. pressure relief nipple.
  2. Cap the supply and return connections.
  3. Connect a 1/2 in. garden hose to the boiler drain valve and fill slowly until the gauge reads 68 psi (4.65 bar).
  4. Hold pressure for 15 minutes. Do not leave the boiler unattended.
  5. Check pipe joints, safety devices and boiler base for leaks with a flashlight.
  6. Release pressure slowly through the drain valve, remove the caps, and install the pressure relief valve.

Applies to: Vitorond 100 VR1 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 VR1 installation and service manual, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.