Viessmann · Boiler troubleshooting

Installing and wiring the outdoor temperature sensor

Vitodens 200-W B2HA

What is going on

Mounting and wiring the outdoor sensor to the boiler control board, including cable limits and placement rules.

Check in this order

  1. Remove the cover of the outdoor temperature sensor.
  2. Mount the wall-mount base with the cable entry pointing downward.
  3. Route the cable from the boiler control board to the outdoor sensor and connect it to the sensor terminals (wires are interchangeable).
  4. Connect the outdoor sensor to terminals X3.1/X3.2 on the boiler control board (wires are interchangeable).
  5. Place the cover on the base and snap it into place.
  6. Cable 2-wire, max. 95 ft (35 m), minimum AWG 16 copper.
  7. Mount the sensor 6.6 to 8.2 ft (2 to 2.5 m) above ground on the north or northwest wall.
  8. On a multi-storey building, mount it in the upper half of the second floor.
  9. Keep the sensor away from windows, doors, air vents, balconies and gutters.
  10. Do not cover the sensor with plaster; allow for plaster thickness or remove the sensor before plastering.
  11. Keep the sensor cable away from line voltage wiring (120/240 V).

Applies to: Models 45, 60

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 49. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.