Weil-McLain · Boiler troubleshooting
Water level drops out of the gauge glass into the returns
What is going on
Water leaves the boiler and backs into the return piping while firing.
Likely causes
- Hartford loop piped wrong
- Check valve stuck or failed
- Vacuum breaker not working
Check in this order
- Compare the near-boiler piping with the piping drawings in the boiler manual, mainly the Hartford loop. Re-pipe if it does not match.
- Clean or replace the check valve.
- Clean or replace the vacuum breaker.
Applies to: SGO-3 to SGO-9 oil-fired steam boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.