Weil-McLain · Boiler troubleshooting

Water level drops out of the gauge glass into the returns

Weil-McLain SGO Series 4

What is going on

Water leaves the boiler and backs into the return piping while firing.

Likely causes

  • Hartford loop piped wrong
  • Check valve stuck or failed
  • Vacuum breaker not working

Check in this order

  1. Compare the near-boiler piping with the piping drawings in the boiler manual, mainly the Hartford loop. Re-pipe if it does not match.
  2. Clean or replace the check valve.
  3. Clean or replace the vacuum breaker.

Applies to: SGO-3 to SGO-9 oil-fired steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.