Choose an outdoor reset heating curve

Vitotron 100 VLN2

What is going on

Pick one of 9 heating curves so the supply temperature matches the outdoor temperature. Use the offset to fine-tune the room temperature.

Check in this order

  1. Find the design outdoor temperature on the horizontal axis (0 to 70 °F).
  2. Follow that point up to the desired supply temperature on the vertical axis.
  3. Choose the curve that crosses at that point. If there is no exact match, choose the closest curve.
  4. Check the choice periodically and change curves if needed.
  5. If the room is too cold or too warm across a wide outdoor range, shift the curve with the offset (-9 °F to +9 °F). Shift down if too warm, up if too cold.

Applies to: Vitotron 100 VLN2 outdoor reset

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotron 100 VLN2 installation and service instructions, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.