Weil-McLain · Boiler troubleshooting

Termination exposure and condensate protection

SlimFit Series 3

What is going on

Do not extend exposed vent pipe beyond the figure dimensions, since condensate can freeze and block the vent. For sidewall runs, exposed outside pipe up to 4 ft needs no insulated enclosure but must be braced at no more than 24 in spacing. Longer exposed run needs an insulated enclosure. In very cold climates, use an insulated chase that allows inspection.

Likely causes

  • Excessive exposed vent length in cold weather
  • Condensate freezing inside exposed pipe

Check in this order

  1. Keep exposed vent pipe within the length shown in the manual figure.
  2. Brace exposed pipe no more than 24 in apart.
  3. Use an insulated enclosure if exposed pipe exceeds 4 ft.
  4. In extremely cold climates, use an insulated chase that allows inspection and keeps insulation dry.

Applies to: Vent terminations and exposed vent piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 28, 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.