Weil-McLain · Boiler troubleshooting

Checking the boiler out (supply) temperature sensor

CGi Series 5

What is going on

Resistance-type sensor. Check its value against the reference table and confirm the control reads temperature correctly.

Check in this order

  1. Measure sensor resistance with an ohmmeter at known temperatures: freezing (32 F), room temp (60-70 F) and boiling at sea level (212 F). For freezing and boiling, put the sensor in water at that temperature.
  2. Compare readings with the sensor resistance table.
  3. To check the control, put a resistance decade box in place of the sensor and confirm the displayed temperature matches the resistance input.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 73. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.