Viessmann · Boiler troubleshooting

Adjust the adjustable high limit from 95°C to 100°C

Vitotronic 300

What is going on

The adjustable high limit ships at 95°C. It can be raised to 100°C (212°F) by breaking off cams on the stop dial. Note the coding address 06 setting after the change.

Check in this order

  1. Disconnect power and lever out the selector knob R behind the hinged cover with a suitable screwdriver.
  2. Use pointed pliers to break off the cams shown shaded in the figure from the stop dial. The adjustment range is 75 to 100°C (167 to 212°F).
  3. Refit selector knob R so the marking sits in the centre of the selected range.
  4. Record the setting of coding address 06.
  5. If the system feeds a domestic hot water tank, make sure the maximum permitted DHW temperature is not exceeded. Fit a suitable safety device if needed.

Applies to: Vitotronic 300 GW2 adjustable high limit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 Installation and Service Instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.