Viessmann · Boiler troubleshooting
Set the fixed high limit to 212 F (100 C)
What is going on
Only do this if needed. The setting cannot be reversed, and the adjustable high limit must not be above 167 F (75 C) afterward.
Check in this order
- Turn the indicator screw at the rear of the FHL to the 212 F (100 C) position with a flat-head screwdriver.
- Complete the protocol on page 34 of the manual.
- Confirm the adjustable high limit is not set above 167 F (75 C).
Applies to: Vitotronic 100 KW10B fixed high limit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 KW10B installation manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.