Viessmann · Boiler troubleshooting

Check fuse F1

Vitodens 100-W B1HE/B1KE

What is going on

Procedure to check the 120 V control fuse F1 in the junction box.

Check in this order

  1. Turn off the ON/OFF switch.
  2. Depending on the configuration, move the programming unit with its bracket to the maintenance position.
  3. Remove cover A.
  4. Check fuse F1 against the connection and wiring diagram.
  5. Insert fuses without force and seat them correctly. Only use the same structural type with the specified response characteristic (6.3 A slow, 120 V).

Applies to: Vitodens 100-W B1HE/B1KE

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 89. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.