Viessmann · Boiler troubleshooting
Boiler will not reset after F2 fault shutdown
What is going on
If the burner control unit will not reset after a fault shutdown (F2) even though boiler water is below about 203°F (95°C), check the fixed high limit switch.
Likely causes
- Faulty fixed high limit switch
Check in this order
- Pull the leads from the fixed high limit.
- Check continuity of the fixed high limit with a multimeter.
- Remove a faulty fixed high limit.
- Coat the replacement fixed high limit with heat conducting paste and install it.
- Reset the control as described on page 76 of the manual.
Applies to: Fault shutdown F2, fixed high limit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.