Boiler will not reset after F2 fault shutdown

Vitodens 100-WWB1B

What is going on

If the burner control unit will not reset after a fault shutdown (F2) even though boiler water is below about 203°F (95°C), check the fixed high limit switch.

Likely causes

  • Faulty fixed high limit switch

Check in this order

  1. Pull the leads from the fixed high limit.
  2. Check continuity of the fixed high limit with a multimeter.
  3. Remove a faulty fixed high limit.
  4. Coat the replacement fixed high limit with heat conducting paste and install it.
  5. Reset the control as described on page 76 of the manual.

Applies to: Fault shutdown F2, fixed high limit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.