Servicing the domestic water inlet manifold (flow transducer and bypass filter)
What is going on
Clean the inlet filter, check the O-ring and bypass filter, then reassemble.
Check in this order
- Follow the gas and electrical shut-off steps and the brazed plate steps 1-4 on the previous page.
- Lift the flow sensor electronic pickup off the flow transducer/turbine, keeping its wire attached.
- Remove the flow transducer/turbine with an 18mm hex socket.
- Detach the filter and clean it by pushing air or water through it, opposite to normal flow. Do not damage the plastic filter.
- Check the O-ring and seat in the inlet manifold. Replace the O-ring if damaged.
- Reassemble the transducer and filter, reinsert into the block and torque to the value in the torque table.
- Push the flow sensor pickup back on and confirm its wires are still connected.
- Remove the bypass filter with a 16mm (5/8 in) wrench. Clean with water if needed. Confirm the spring is relaxed and in good condition.
- Reinsert the bypass and torque to the value in the torque table.
- The boiler inlet water temperature sensor sits in this manifold. Verify it using the temperature sensor check.
Applies to: 80/110/150/199 Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 157. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.