Weil-McLain · Boiler troubleshooting
ECO Tec S2 locked out by an external limit (J20)
What is going on
External limits can be wired as manual reset (J20 pins 1-2) or auto reset (J20 pins 3-4). A jumper is fitted from the factory on each pair.
Likely causes
- Device wired on J20 pins 1-2 opened (manual reset lockout)
- Device wired on J20 pins 3-4 opened (auto restart)
- Factory jumper missing
Check in this order
- Find which limit is wired to J20 and why it opened.
- Pins 1-2 boiler goes into manual lockout and the alarm contact on J18 pins 4-5 closes. The limit must close, then reset the control by hand.
- Pins 3-4 boiler stops while the limit is open and restarts on its own 150 seconds after it closes.
- No external limit used make sure the factory jumpers are still on both pairs.
- The J18 alarm contact closes on manual lockout only (rated 24 VAC or less, 0.5 A or less).
Applies to: ECO Tec 80/110/150/199 Series 2 heating only
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Field wiring F/H p.63-64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.