Variable speed boiler pump setup (0-10 VDC output)
What is going on
The 0-10 VDC output drives a variable speed boiler pump. Voltages are set in Manual Test Mode for each firing rate.
Check in this order
- Connect the 0-10 VDC output to the pump's 0-10 VDC input.
- Open Contractor menu, Diagnostics, Manual Test Mode.
- Highlight FORCE RATE, press EDIT, choose HIGH, then SAVE.
- Adjust pump volts until the desired delta T on the boiler is reached, then SAVE AS MAX VOLTS.
- Set Pump Volts back to AUTO and repeat for each FORCE RATE speed, including ignition speed.
- Confirm operating voltages VARIABLE SPEED MAX RATE VOLTS, VARIABLE SPEED MIN RATE VOLTS, and VOLTS WHEN BURNER OFF.
Applies to: Variable speed boiler pump
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Advanced Manual, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.