Weil-McLain · Boiler troubleshooting

Variable speed boiler pump setup (0-10 VDC output)

Evergreen Series 2

What is going on

The 0-10 VDC output drives a variable speed boiler pump. Voltages are set in Manual Test Mode for each firing rate.

Check in this order

  1. Connect the 0-10 VDC output to the pump's 0-10 VDC input.
  2. Open Contractor menu, Diagnostics, Manual Test Mode.
  3. Highlight FORCE RATE, press EDIT, choose HIGH, then SAVE.
  4. Adjust pump volts until the desired delta T on the boiler is reached, then SAVE AS MAX VOLTS.
  5. Set Pump Volts back to AUTO and repeat for each FORCE RATE speed, including ignition speed.
  6. Confirm operating voltages VARIABLE SPEED MAX RATE VOLTS, VARIABLE SPEED MIN RATE VOLTS, and VOLTS WHEN BURNER OFF.

Applies to: Variable speed boiler pump

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Series 2 Advanced Manual, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.