Provisional burner operation with external dry contact (BMS)
What is going on
Use this to hand heat demand and modulation to an external controller.
Check in this order
- Remove the jumper across terminals 23 (L) and 24 (L).
- Connect terminals 23 (L) and 25 (L) to an external dry contact (heat demand on close).
- On demand the boiler holds low fire until the BMS controls modulation.
- Wire the BMS modulation contacts to T6, T7 and T8 at plug 90 as described in the manual.
Applies to: Vitotronic 300 GW6B with burner interface
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300, GW6B installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.