Viessmann · Boiler troubleshooting

Provisional burner operation with external dry contact (BMS)

Vitotronic 300

What is going on

Use this to hand heat demand and modulation to an external controller.

Check in this order

  1. Remove the jumper across terminals 23 (L) and 24 (L).
  2. Connect terminals 23 (L) and 25 (L) to an external dry contact (heat demand on close).
  3. On demand the boiler holds low fire until the BMS controls modulation.
  4. Wire the BMS modulation contacts to T6, T7 and T8 at plug 90 as described in the manual.

Applies to: Vitotronic 300 GW6B with burner interface

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, GW6B installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.