Ignition electrode and ignition wiring check
What is going on
Annual check of the ignitor, ignition cable and ground wiring.
Likely causes
- White oxide buildup on the electrode
- Worn or damaged ignitor insulation
- Poor ground continuity
Check in this order
- Remove the ignition electrode from the heat exchanger access cover.
- Clean white oxides off with steel wool. If it cannot be cleaned satisfactorily, replace the ignitor.
- Reinstall the electrode with its gasket in good condition and correctly positioned.
- Make sure the two electrodes are parallel.
- Measure ignition cable resistance. A good cable reads 900 to 1000 ohms. Replace if not in range.
- Inspect the ground wire from the heat exchanger access cover to the ground terminal strip.
- Check ground continuity with a continuity meter. Replace ground wires if results are not satisfactory.
- Verify all wiring is in good condition and securely attached.
Applies to: Ultra Series 4 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 gas-fired water boiler manual, p. 111-112. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.