Ignition electrode and ignition wiring check

Ultra Series 4

What is going on

Annual check of the ignitor, ignition cable and ground wiring.

Likely causes

  • White oxide buildup on the electrode
  • Worn or damaged ignitor insulation
  • Poor ground continuity

Check in this order

  1. Remove the ignition electrode from the heat exchanger access cover.
  2. Clean white oxides off with steel wool. If it cannot be cleaned satisfactorily, replace the ignitor.
  3. Reinstall the electrode with its gasket in good condition and correctly positioned.
  4. Make sure the two electrodes are parallel.
  5. Measure ignition cable resistance. A good cable reads 900 to 1000 ohms. Replace if not in range.
  6. Inspect the ground wire from the heat exchanger access cover to the ground terminal strip.
  7. Check ground continuity with a continuity meter. Replace ground wires if results are not satisfactory.
  8. Verify all wiring is in good condition and securely attached.

Applies to: Ultra Series 4 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 111-112. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.