Viessmann · Boiler troubleshooting
Replace solenoid valve (2/2 directional valve)
What is going on
Solenoid valve replacement on CA3B 2.5 and 3.0 models.
Check in this order
- Remove the hose clips and the hoses. Unscrew the 2 plastic brackets from the 2/2 directional valve.
- Unscrew the 2 fixing screws and remove the 2/2 directional valve.
- Install in reverse order. Tighten to 1.1 lb.ft (1.5 Nm).
- Screw the plastic brackets into the new valve.
- Fit the hoses and secure with hose clips. Match the valve marking: 1 left, 2 right.
Applies to: CA3B 2.5 and 3.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 65. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.