Convert SlimFit boiler from natural gas to propane

SlimFit Series 3

What is going on

Boilers ship set for natural gas. Propane needs a propane orifice, and the Model 750 also needs a blower orifice. The conversion kit is supplied with the boiler.

Check in this order

  1. Shut off the gas supply and the electrical power, and let the boiler cool before starting.
  2. Install the propane orifice at the orifice location on the boiler. Confirm the orifice size marking matches the boiler size.
  3. On Model 750, install the propane blower orifice from the conversion kit.
  4. On SF-550 the blower plate is used for both natural gas and propane. On SF-750 propane requires the blower plate, which is not used on natural gas.
  5. Start up and fully test the boiler after conversion to confirm performance.
  6. Only a qualified installer, service agency or gas supplier should do the conversion, following the kit instructions.

Applies to: SlimFit 550 and 750 MBH on propane

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 3 boiler manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.