Check or change rotational direction of mixing valve motor
What is going on
After power-up the boiler runs a self-test that opens and closes the mixing valve. If the flow temperature drops when the valve is opened, the motor direction or valve fitting is wrong.
Likely causes
- Motor turning in wrong direction
- Mixing valve set incorrectly fitted
Check in this order
- Set the mixing valve manually to Open after the self-test.
- Confirm the flow temperature sensor reads a higher temperature.
- If the temperature drops, remove the upper casing cover of the extension kit.
- At plug gS, switch the cores at terminals '|' and '~'.
- Refit the casing cover.
- Disconnect main power before opening the boiler.
Applies to: Mixing valve extension kit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 88. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.