Check or change rotational direction of mixing valve motor

Vitodens 200-W B2HA

What is going on

After power-up the boiler runs a self-test that opens and closes the mixing valve. If the flow temperature drops when the valve is opened, the motor direction or valve fitting is wrong.

Likely causes

  • Motor turning in wrong direction
  • Mixing valve set incorrectly fitted

Check in this order

  1. Set the mixing valve manually to Open after the self-test.
  2. Confirm the flow temperature sensor reads a higher temperature.
  3. If the temperature drops, remove the upper casing cover of the extension kit.
  4. At plug gS, switch the cores at terminals '|' and '~'.
  5. Refit the casing cover.
  6. Disconnect main power before opening the boiler.

Applies to: Mixing valve extension kit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 88. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.