Outdoor temperature sensor installation
What is going on
Mount the outdoor sensor 2 to 2.5 m (6.5 to 8 ft) above ground on a north or north-west wall. In multi-storey buildings, mount it in the upper half of the second storey. Keep it away from windows, doors, vents, balconies and gutters, and do not paint the housing.
Check in this order
- Remove the sensor cover.
- Mount the rear section to the wall with field-supplied hardware.
- Feed the wire into the strain relief at the bottom of the housing.
- Connect the wire to the sensor terminals and tighten.
- Refit the cover.
- Plug the 2-pole plug into socket F9 on the control.
Applies to: Outdoor temperature sensor AF S
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 installation manual, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.