Gas piping pressure test
What is going on
Test gas piping and remove air before the boiler is put into operation.
Check in this order
- Isolate the boiler from the gas piping using its manual shutoff valve for tests at or below ½ psig (14 in. w.c.).
- Disconnect the boiler and its shutoff valve for tests above ½ psig (14 in. w.c.).
- Perform the leak test with approved liquid spray solution.
- Keep leak fluid off electrical parts, wires and connectors, and off the gas valve regulator and its vent opening.
- Correct all leaks found.
- Purge air from the gas line.
Applies to: All models
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A installation instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.