Weil-McLain · Boiler troubleshooting

Metal flakes in the flue ways (oil steam boiler)

Weil-McLain SGO Series 4

What is going on

Flaking or corrosion found in the flue passages or vent.

Likely causes

  • Contaminated combustion air (cleaners, chemicals, sprays near the boiler)
  • Flue gas condensing in the flue ways because of a low firing rate or bad combustion

Check in this order

  1. Remove chemical products stored near the boiler, or bring in outside air for combustion.
  2. Check the burner nozzle size and oil pump pressure against the rating label for the right firing rate.
  3. Set combustion with an analyzer, not by eye.
  4. Clean the flue ways.

Applies to: SGO-3 to SGO-9 oil-fired steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.