Clocking the natural gas meter to verify burner input
What is going on
Time the meter to calculate the boiler input in Btu/h and confirm it is correct. A boiler under-fired by 5% is acceptable. Do not over-fire the boiler.
Check in this order
- Contact the gas utility for the correct heating value before timing the meter.
- Turn off all other gas appliances served by the meter.
- Time how many seconds the boiler takes to use 10 cu ft of gas.
- Divide 3600 times 10 by the seconds to get cu ft per hour, then multiply by the heating value to get Btu/h input.
- Example 240 seconds at 1000 Btu/cu ft gives 150,000 Btu/h, which is correct for a Vitodens 100-W 150.
Applies to: Gas meter verification
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.