Clocking the natural gas meter to verify burner input

Vitodens 100-WB1HEB1KE

What is going on

Time the meter to calculate the boiler input in Btu/h and confirm it is correct. A boiler under-fired by 5% is acceptable. Do not over-fire the boiler.

Check in this order

  1. Contact the gas utility for the correct heating value before timing the meter.
  2. Turn off all other gas appliances served by the meter.
  3. Time how many seconds the boiler takes to use 10 cu ft of gas.
  4. Divide 3600 times 10 by the seconds to get cu ft per hour, then multiply by the heating value to get Btu/h input.
  5. Example 240 seconds at 1000 Btu/cu ft gives 150,000 Btu/h, which is correct for a Vitodens 100-W 150.

Applies to: Gas meter verification

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.