Viessmann · Boiler troubleshooting
Remove the burner assembly
What is going on
Remove the burner for inspection or cleaning. Do not lay the burner on its cylindrical tube or touch the tube mesh.
Check in this order
- Switch off the main power and the ON/OFF switch 8.
- Close the gas shut-off valve and secure it against reopening.
- Remove the front upper panel (page 11).
- Flip down the control console (page 11).
- Remove the boiler inner cover.
- Unplug the cables from fan motor A, gas valve B, ionization electrode C, ignition unit D and ground wire E.
- Disconnect the gas supply pipe fitting F.
- Remove four Torx screws G.
- Remove the burner assembly.
Applies to: Vitodens 222-F B2TB 19, 35, 68, 125
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB service instructions, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.