Viessmann · Boiler troubleshooting

Check burner refractory ring and cylinder burner

Vitodens 200-W

What is going on

Check the burner refractory ring and cylinder burner assembly for damage and replace if needed.

Check in this order

  1. Remove the electrode block and ionization electrode.
  2. Undo the three retaining clips and remove the refractory ring.
  3. Loosen the four Torx screws and remove the cylinder burner assembly and assembly gasket.
  4. Fit the new cylinder burner assembly and new gasket. Tighten to 3.3 lb.ft (4.5 Nm) with a calibrated torque wrench.
  5. Refit the refractory ring and secure with the retaining clips.
  6. Refit the electrode block and ionization electrode. Tighten to 2.6 lb.ft (3.5 Nm) with a calibrated torque wrench.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.