Viessmann · Boiler troubleshooting

Fixed high limit has tripped (lockout)

Vitotronic 100 GC1

What is going on

The fixed high limit shuts the boiler down with lockout when the water temperature reaches its limit. It is reset manually. It also locks out on a capillary leak or when ambient is below -10 °C / 14 °F.

Likely causes

  • Boiler water reached the fixed high limit setting
  • Capillary leak
  • Ambient temperature below -10 °C / 14 °F

Check in this order

  1. Check the boiler water temperature and the limit setting.
  2. Check the capillary and the ambient temperature at the limit.
  3. Test the limit with its test button.
  4. Reset the fixed high limit manually once the cause is cleared.

Applies to: Fixed high limit on Vitotronic 100 GC1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 and 300-K MW1S installation and service instructions, p. 121. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.