Weil-McLain · Boiler troubleshooting
Reinstalling the brazed plate heat exchanger and inlet manifold gaskets
What is going on
Four new gaskets must be used on the DHW inlet and return connections to seal the brazed plate exchanger.
Check in this order
- Install four new gaskets in the DHW inlet and DHW return plate connections.
- Slide the brazed plate into the rear of the enclosure with the 'This side up' label facing up.
- Lift the plate slightly to align with the DHW connections, reinstall the two Allen head screws and tighten to the torque in the torque table.
- Make sure gaskets are in good condition and aligned before tightening.
- Open the CH supply and return valves and fill the boiler. Purge all air and check every joint for leaks.
- Open the DHW cold inlet and DHW hot outlet valves, flush through a fixture and check for leaks.
- Restore gas and power per the operating instructions. The 3-way valve may be toggled to bleed air. Run the 3-way valve test (page 143).
- Reset and clear any faults that occurred during service.
Applies to: 80/110/150/199 Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 157. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.