Weil-McLain · Boiler troubleshooting
Monthly venting system inspection
What is going on
Visual vent check plus draft test on draft hood models.
Likely causes
- Blockage in the flue or vent system
- Leaking or deteriorated vent joints
- Vent damper not opening before ignition
Check in this order
- Visually inspect the full flue gas vent system for blockage, leaks, deteriorated piping and loose joints.
- On CGa, EG and LGB Series 2 boilers with the burner firing, hold a lit candle or match just below the lower edge of the draft hood skirt.
- If the flame burns steadily, the vent is drafting properly.
- If the flame blows out or flickers badly, check the vent for obstructions or other venting faults.
- Verify the vent damper opens before the burners light.
- Tell the service technician right away about any problem found.
Applies to: CGa, EG, LGB Series 2 (draft test); all models (visual check)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.