Route the pressure relief valve discharge

Vitocrossal 200 CI2

What is going on

The relief valve discharge must be at least the outlet size, run horizontally over the side of the boiler, then drop vertically to about 1 ft (300 mm) above the floor, close to a floor drain.

Check in this order

  1. Keep the discharge pipe the same size as the valve outlet.
  2. Run the pipe horizontally over the side of the boiler, then vertically down.
  3. End the pipe about 1 ft (300 mm) above the floor, as close to a floor drain as possible.
  4. Do not pipe the discharge outdoors or to an area where it can freeze.
  5. Secure the discharge pipe with hangers or brackets.
  6. Do not install any valve or obstruction between the boiler and the relief valve, or on its discharge side.

Applies to: Pressure relief valve

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 installation instructions, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.